We always believe that one's character decides products' quality, the details decides products' high-quality ,together with the REALISTIC,EFFICIENT AND INNOVATIVE crew spirit for High Pressure Water Mist Gun, Mist Sprinkler, Protline Linear Heat Detector, sincerity and strength ,always keep approved good quanlity ,welcome to our factoty for visit and instruction and business.
High definition Linear Heat Detector For Tank - Linear Heat Detector NMS2001 Cable – Anbesec Detail:

MicroSenseWire Analog Linear Heat Detector –NMS2001, consists of four cores with high performance and good adaptability, is widely used in industrial, commercial, and other over-heat hazardous sites.

Structure and how it works

NMS2001 – LHD cable consists of four cores (red and white) twisting together, and the outer jacket is made from heat-resisting material—PVC, strengthening the durability and the reliability. The material of outer jacket can be changed in order to meet the requirements of different environments, chemical resistance material and anti-UV material.

The structure is shown below:

The NMS2001 – LHD cable has high performance of fire retardance, consists of four cores made from special insulating layer material–NTC (negative temperature coefficient). The terminal unit can indicate the change of system temperature through monitoring the change of resistance value.

During wire connection and installation, two parallel red cables and two parallel white cables are connected to control unit and terminal unit, formulating a loop circuit.

2
2132321

The system detects the resistance fluctuation of Linear Heat Detection Cable resulted from the fluctuation of circuit temperature–i.e. when temperature rises, resistance drops. This fluctuation is monitored through linear detector Control Unit of Linear Heat Detection Cable. When it reaches preset alarm threshold value, output alarming signal. This feature allows the system to have the ability to detect the fire in point or in line of whole circuit, which is that the system could detect the temperature fluctuation in certain point as well as certain area. After alarming, it could automatically restore to working condition.

General length of finished product is 500m per reel. Longer length is not recommended, due to the feature of analog signal. The alarm temperature is related to the length of LHD cable, so it is suggested to make the alarm test with 2m LHD cable. If the alarm temperature is set at 105℃, test with 5m LHD cable, the alarm temperature may be lower, on the contrary, the alarm temperature may be higher.

Features

♦ High adaptability: it could be applied in narrow areas , harsh and hazardous environments;

♦ Great compatibility: NMS2001-I Linear Detector Control Unit has relay output, which could be connected to various fire alarm control panel mainframes;

♦ Chemical resistance and abrasion resistance: extrude and make jacket with high-strength, which could meet different needs;

Re-settable: the LHD cable could automatically reset after alarming (under the situation of fire alarming temperature does not harm linear heat detection cable), saving much cost for maintenance and operation;

Multiple monitoring functions: except for normal fire alarm, fault of open circuit or short circuit;

♦ Good anti-EMI interference (Interruption resistance): four-core stranded structure has strong ability to resist electromagnetic field interruption, and

♦ Easy installation and maintenance.

FeaturesApplications

♦ Cable tray

♦ Conveyor belt

♦ Power distribution equipments: switch cabinet, transformer, transformer station and motor control center

♦ Dust collector and bag type dust collector

♦ Warehouse and rack storage

♦ Industrial material processing system

♦ Bridge, wharf and vessel

♦ Chemicals storage facilities

♦ Aircraft hangar and oil depot

NMS2001 system connection

523523

Notice:

1. It is suggested that terminal unit and connected fire alarm control panel shall be reliably grounded.

2. Forbid bending or turning the LHD cable with an acute angle, and the minimum bending radius of the LHD cable should not be less than 150mm preventing from damage.

3. The product shall be well packed during the shipment, forbidding damage.

4. It is suggested to test the detector annually, the normal resistance between the cores shall not be less than 50MΩ, otherwise, please replace. Test equipment: 500V megger.

5. It is not allowed to maintain the detector without contacting our company.


Product detail pictures:

High definition Linear Heat Detector For Tank - Linear Heat Detector NMS2001 Cable  – Anbesec detail pictures


Related Product Guide:

Sticking to the principle of "Super Quality, Satisfactory service" ,We are striving to be a good business partner of you for High definition Linear Heat Detector For Tank - Linear Heat Detector NMS2001 Cable – Anbesec , The product will supply to all over the world, such as: Anguilla, Guatemala, Malaysia, Our company has built stable business relationships with many well-known domestic companies as well as oversea customers. With the goal of providing high quality products to customers at low cots, we are committed to improving its capacities in research, development, manufacturing and management. We have honored to receive recognition from our customers. Till now we have passed ISO9001 in 2005 and ISO/TS16949 in 2008. Enterprises of "quality of survival, the credibility of development" for the purpose, sincerely welcome domestic and foreign businessmen to visit to discuss cooperation.
  • The company's products very well, we have purchased and cooperated many times, fair price and assured quality, in short, this is a trustworthy company!
    5 Stars By Judy from Argentina - 2018.11.06 10:04
    The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly
    5 Stars By Poppy from Angola - 2018.07.27 12:26

    Send your message to us: