With our leading technology also as our spirit of innovation,mutual cooperation, benefits and development, we are going to build a prosperous future jointly with your esteemed company for Water Mister System Parts, Stand Alone Water Mist System, Hospital Fire Fighting, We sincerely hope to determine some satisfactory interactions with you in the in the vicinity of long term. We'll hold you informed of our progress and stay up for building steady small business relations along with you.
OEM Manufacturer Tunnel Fire Detectors - NMS2001-I Control Unit – Anbesec Detail:

NMS2001-I is applied to detect the change of sensing cable’s temperature, and negotiate with the fire alarm control panel.

NMS2001-I can monitor the fire alarm , open circuit and short circuit of the detected area constantly and  continuously, and indicate all the data on the  light indicator. NMS2001-I shall be reset after power-off and on, due to its function of fire alarm locking. Correspondingly, the function of fault alarm can be reset automatically after fault clearance, NMS2001-I is powered by DC24V, so please pay attention to power capacity and power cord.

Features of NMS2001-I

♦ Plastic shell: Chemical resistance, aging resistance and shocking resistance;

♦ Simulation test of fire alarm or fault alarm can be conducted. Friendly operation

♦ IP rating: IP66

♦ With LCD, Various alarming information could be shown

♦ The detector has high ability of interruption resistance adopting fine grounding measurement, isolation test and software interruption resistance technique. It is able to apply in places with high electromagnetic field interruption.

Shape profile and connection instruction of NMS2001-I:

123

Chart 1 Shape profile of NMS2001-I

Installation instruction

21323

Chart 2 Connecting terminals on Control Unit

DL1, DL2:  DC24V power supply, non-polar connection

1, 2, 3, 4: with sensing cable

terminal

COM1 NO1: pre-alarm/fault/fun, relay contact composite output

EOL1: with terminal resistance 1

(to match the input module, corresponding to COM1 NO1)

COM2 NO2: fire/fault/fun , relay contact composite output

EOL2: with terminal resistance 1

(to match the input module, corresponding to COM2 NO2)

(2)connection instruction of the end port of sensing cable

Make two red cores together, and so two white cores, then make water-proof packing.

Usage and operation of NMS2001-I

After the connection and installation, turn on the control unit, then the green indicator light blinks for one minute. Followed that, the detector could go normal state of monitoring, the green indicator light is on constantly. The operation and set could be handled on the LCD screen and buttons.

(1) Operation and set displaying

Displaying of normal running :

NMS2001

Displaying after pressing“Fun” :

Alarm Temp
Ambient Temp

Press “△” and “▽” to choose the operation, then press “OK” for confirmation into the menu, press “C” for returning the previous menu.

The menu design ofNMS2001-I is shown as following:

1111

Press “△” and “▽” to change the current data in the secondary interface“1.Alarm Temp”, “2.Ambient Temp”, “3.Using Length”;

Press “C” to the previous set data, and “OK” to the next data;press “OK” at the end of current data for confirming the set and back to the previous menu, press “C” at the beginning of the current data to cancel the set and back to the previous menu.

(1) Set of fire alarm temperature

The fire alarm temperature could be set from 70℃ to 140℃, and the default setting of pre-alarm temperature is 10℃ lower than the fire alarm temperature.

(2) Set of ambient temperature

The maximum ambient temperature of detector could be set from 25℃ to 50℃, it may help the detector to adjust the adaptation to the working environment.

(3) Set of working length

The length of the sensing cable could be set from 50m to 500m.

(4) Fire test, fault test

The connectivity of the system could be tested in the menu of fire test and fault test.

(5) AD monitor

This menu is designed for AD check.

The alarm temperature is in proportion to the ambient temperature and the using length theoretically, set the alarm temperature, the ambient temperature and the using length rationally, so that the stability and the reliability could be improved.


Product detail pictures:

OEM Manufacturer Tunnel Fire Detectors - NMS2001-I Control Unit  – Anbesec detail pictures


Related Product Guide:

Innovation, excellent and reliability are the core values of our company. These principles today much more than ever form the basis of our success as an internationally active mid-size business for OEM Manufacturer Tunnel Fire Detectors - NMS2001-I Control Unit – Anbesec , The product will supply to all over the world, such as: Belgium, Kuala Lumpur, Uganda, At Present, our merchandise have been exported to more than sixty countries and different regions, such as Southeast Asia, America, Africa, Eastern Europe, Russia, Canada etc. We sincerely hope to establish wide contact with all potential customers both in China and the rest part of the world.
  • The supplier abide the theory of "quality the basic, trust the first and management the advanced" so that they can ensure a reliable product quality and stable customers.
    5 Stars By Amelia from France - 2018.11.02 11:11
    This manufacturer can keep improving and perfecting products and service, it is in line with the rules of market competition, a competitive company.
    5 Stars By Maggie from Serbia - 2017.11.12 12:31

    Send your message to us: