Our mission should be to turn out to be an innovative supplier of high-tech digital and communication devices by furnishing benefit added design and style, world-class manufacturing, and repair capabilities for Types Of Linear Heat Detector, Stand Alone Water Mist System, Water Mist System Descends, The team of our company with the use of cutting-edge technologies delivers impeccable quality products supremely adored and appreciated by our customers worldwide.
Special Price for Conveyor Belt Fire Detection Systems - Linear Heat Detector NMS2001 Cable – Anbesec Detail:

MicroSenseWire Analog Linear Heat Detector –NMS2001, consists of four cores with high performance and good adaptability, is widely used in industrial, commercial, and other over-heat hazardous sites.

Structure and how it works

NMS2001 – LHD cable consists of four cores (red and white) twisting together, and the outer jacket is made from heat-resisting material—PVC, strengthening the durability and the reliability. The material of outer jacket can be changed in order to meet the requirements of different environments, chemical resistance material and anti-UV material.

The structure is shown below:

The NMS2001 – LHD cable has high performance of fire retardance, consists of four cores made from special insulating layer material–NTC (negative temperature coefficient). The terminal unit can indicate the change of system temperature through monitoring the change of resistance value.

During wire connection and installation, two parallel red cables and two parallel white cables are connected to control unit and terminal unit, formulating a loop circuit.

2
2132321

The system detects the resistance fluctuation of Linear Heat Detection Cable resulted from the fluctuation of circuit temperature–i.e. when temperature rises, resistance drops. This fluctuation is monitored through linear detector Control Unit of Linear Heat Detection Cable. When it reaches preset alarm threshold value, output alarming signal. This feature allows the system to have the ability to detect the fire in point or in line of whole circuit, which is that the system could detect the temperature fluctuation in certain point as well as certain area. After alarming, it could automatically restore to working condition.

General length of finished product is 500m per reel. Longer length is not recommended, due to the feature of analog signal. The alarm temperature is related to the length of LHD cable, so it is suggested to make the alarm test with 2m LHD cable. If the alarm temperature is set at 105℃, test with 5m LHD cable, the alarm temperature may be lower, on the contrary, the alarm temperature may be higher.

Features

♦ High adaptability: it could be applied in narrow areas , harsh and hazardous environments;

♦ Great compatibility: NMS2001-I Linear Detector Control Unit has relay output, which could be connected to various fire alarm control panel mainframes;

♦ Chemical resistance and abrasion resistance: extrude and make jacket with high-strength, which could meet different needs;

Re-settable: the LHD cable could automatically reset after alarming (under the situation of fire alarming temperature does not harm linear heat detection cable), saving much cost for maintenance and operation;

Multiple monitoring functions: except for normal fire alarm, fault of open circuit or short circuit;

♦ Good anti-EMI interference (Interruption resistance): four-core stranded structure has strong ability to resist electromagnetic field interruption, and

♦ Easy installation and maintenance.

FeaturesApplications

♦ Cable tray

♦ Conveyor belt

♦ Power distribution equipments: switch cabinet, transformer, transformer station and motor control center

♦ Dust collector and bag type dust collector

♦ Warehouse and rack storage

♦ Industrial material processing system

♦ Bridge, wharf and vessel

♦ Chemicals storage facilities

♦ Aircraft hangar and oil depot

NMS2001 system connection

523523

Notice:

1. It is suggested that terminal unit and connected fire alarm control panel shall be reliably grounded.

2. Forbid bending or turning the LHD cable with an acute angle, and the minimum bending radius of the LHD cable should not be less than 150mm preventing from damage.

3. The product shall be well packed during the shipment, forbidding damage.

4. It is suggested to test the detector annually, the normal resistance between the cores shall not be less than 50MΩ, otherwise, please replace. Test equipment: 500V megger.

5. It is not allowed to maintain the detector without contacting our company.


Product detail pictures:

Special Price for Conveyor Belt Fire Detection Systems - Linear Heat Detector NMS2001 Cable  – Anbesec detail pictures


Related Product Guide:

We also provide item sourcing and flight consolidation solutions. We have now our very own manufacturing facility and sourcing place of work. We could provide you with nearly every kind of merchandise associated to our merchandise variety for Special Price for Conveyor Belt Fire Detection Systems - Linear Heat Detector NMS2001 Cable – Anbesec , The product will supply to all over the world, such as: panama, Gambia, Pakistan, As an experienced manufacturer we also accept customized order and we could make it the same as your picture or sample specification. The main goal of our company is to live a satisfactory memory to all the customers, and establish a long term business relationship with buyers and users all over the world.
The factory workers have rich industry knowledge and operational experience, we learned a lot in working with them,we are extremely grateful that we can encount a good company has excellent wokers.
5 Stars By Madeline from Angola - 2017.09.09 10:18
The customer service staff is very patient and has a positive and progressive attitude to our interest, so that we can have a comprehensive understanding of the product and finally we reached an agreement, thanks!
5 Stars By Sandy from Grenada - 2018.12.30 10:21

Send your message to us: